Panel Design Tools

Transformer Sizing Calculator

Estimate transformer kVA from connected load, demand factor, future growth, loading margin, ambient derating, and standard rating series.

Inputs
Result
250kVA

Connected load is 235 kVA. After demand, growth, loading margin, and ambient derating, the required rating is 247 kVA.

Demand load165 kVA
Design load198 kVA
Ambient derate100%
Secondary FLC361 A
Next checks
  • Use secondary current for first-pass breaker, cable, and busbar checks.
  • Confirm transformer standard series, impedance, cooling class, harmonics, inrush, and local code before procurement.
Ask VIOX

Transformer kVA sizing equation

Transformer sizing starts by converting the connected load to kVA, then applies demand, growth, loading margin, and ambient derating.

kW input
Sconnected = PPF
hp motor input
Sconnected = hp×0.746 ηPF
Design load
Sdesign = SconnectedD(1+G)
Required transformer rating
Sreq = Sdesign LtargetKambient
Secondary full-load current
Isec = Sstd×1000 3Vsec

where:

Sconnected
Connected apparent load[kVA]
P
Connected real power[kW]
PF
Power factor
hp
Motor horsepower input
η
Motor efficiency as a decimal
D
Demand factor as a decimal
G
Future growth allowance as a decimal
Ltarget
Target transformer loading as a decimal
Kambient
Ambient temperature derating factor
Sreq
Required transformer rating before standard rounding[kVA]
Sstd
Selected standard transformer rating[kVA]
Isec
Secondary full-load current[A]
Vsec
Secondary voltage[V]

For single-phase transformers, the current equation removes √3. Final selection should also check impedance, inrush, harmonics, cooling class, and enclosure conditions.

Assumptions

  • Ambient derate uses an approximate 1% capacity reduction per C above 30 C
  • Target loading represents normal operating margin, commonly 75-80%
  • Standard rating series is a planning reference

Important Warnings

  • Final transformer selection must check inrush, impedance, harmonics, cooling class, enclosure, temperature rise, and applicable standards.
  • Do not use this as a certified transformer specification.

FAQ

Why divide by target loading?

A transformer intended to run at 80% normal loading needs a nameplate rating larger than the design load.

Why does ambient temperature increase the size?

Hot ambient conditions reduce transformer cooling capacity, so the required nameplate kVA increases.