Motor Control Tools

Motor Current Calculator

Estimate motor full-load current and a starting overload relay setting range from motor power, voltage, efficiency, and power factor.

Inputs
Result
14.0A FLC

Estimated motor full-load current is 14.0 A. A 115% reference gives 16.1 A.

Motor output7.50 kW
Estimated FLC14.0 A
Overload reference16.1 A
Efficiency90.0%
Next checks
  • Use motor nameplate current for final overload relay setting.
  • Select contactor by utilization category, voltage, duty, and coordination type.
Ask VIOX

Formula and Method

Three-phase motor FLC = output power / (sqrt(3) x voltage x power factor x efficiency). Horsepower is converted to watts before calculation.

Assumptions

  • Three-phase motor
  • Nameplate data is not available
  • Overload setting is a starting reference only

Important Warnings

  • Motor protection settings must follow the motor nameplate, starter type, duty, and applicable standard.
  • Starting current, utilization category, and coordination are not selected here.

FAQ

Can this select a contactor size?

It provides a current estimate. Contactor selection also needs utilization category, voltage, duty, and coordination requirements.

Should overload relay setting equal breaker size?

No. Overload protection and short-circuit protection have different jobs and are selected differently.