Three Phase Current Calculator

Calculate three-phase current from kW or kVA, line voltage, power factor, and efficiency.

Inputs
Result
48.1A

Balanced three-phase current is approximately 48.1 A at 400 V line voltage.

Input30.0 kw
Equivalent kVA33.3 kVA
Line voltage400 V
Power factor0.90
Next checks
  • Use this current for preliminary feeder and protection checks.
  • Check starting current separately for motors and transformer loads.
Ask VIOX

Formula and Method

For kW input, I = kW x 1000 / (sqrt(3) x V x PF x efficiency). For kVA input, I = kVA x 1000 / (sqrt(3) x V).

Assumptions

  • Balanced three-phase load
  • Line-to-line voltage input

Important Warnings

  • Starting current and harmonics are not included.
  • Use actual equipment nameplate data for final selection.

FAQ

Should I enter phase voltage or line voltage?

Enter line-to-line voltage, such as 400 V, 480 V, or 690 V.

Why is power factor ignored for kVA?

kVA is apparent power, so current can be calculated directly from apparent power and voltage.